1、英文文献 ENERGY SYSTEMS AND ELECTRICAL NETWORKS TECHNICALSTATE OF BASIC EQUIPMENT OF SUBSTATIONS AND OVERHEAD TRANSMISSION LINES AND MEASURES FOR RAISING THEIR RELIABILITY Abstract A brief description of the state of basic equipment employed in 110 750-kV power networks is presented. Problems arising in
2、 operation of this equipment are outlined and recommendations on improving its reliability are made. Transformer equipment, high-voltage circuit breakers, disconnectors, measuring transformers, nonlinear overvoltage suppressors, and transmission lines are considered. Keywords: transformer equipment;
3、 high-voltage circuit breakers; disconnectors,;measuring transformers; overvoltage suppressors; transmission lines; service life. The existing 110 750-kV power networks have been created in the Soviet Union and are now experiencing the following problems: a large volume of time-worn electric equipme
4、nt at substations; poor controllability of the network and inadequate volume of devices for voltage control; low design reliability of the active transmission lines; outdated design of overhead lines; use of some outdated technologies and kinds of network equipment and control systems; low level of
5、automation of network objects and absence of fully automated substations; inadequate performance specification and maintenance of network facilities; high operating costs. A great part of the installed equipment has exhausted standardized minimum service life. It should be noted that different kinds
6、 of equipment have different load-lives. On the average, the substation equipment has been worn out by about 40%. Requirements on reliability of the base facilities are standardized only in GOST 68778 for ac circuit breakers rated for over 1000 V. The GOST68778State Standard also includes requiremen
7、ts on the mechanical life evaluated in terms of parameter N specified for every kind of circuit breaker. For overhead transmission lines N is usually equal to 1000 on-off cycles .However, in the actual practice overhead circuit breakers rated for 330 500 kV fail after 240 380 cycles. We can see that
8、 the reliability of the base power equipment can be evaluated only with the help of operational data. Russian transmission lines are chiefly equipped with air circuit breakers. SF6 circuit breakers constitute only 4% of the total number of employed breakers. The efficiency of operation of these four
9、 percent cannot be analyzed at present due to the absence of enough data in their failures.The reliability of nonlinear overvoltage suppressors (OVS) fabricated by various domestic producers is declared in performance specifications, where their service life is limited to 25 (or 30) years with a pro
10、bability of 0.98. This means that 0.8 (or 0.67) out of 1000 OVS can fail every year. These declared data have not been confirmed yet by operational experience. Transformer equipment. Transformers, autotransformers (AT), and shunting reactors are reliable facilities at substations. The relatively hig
11、h level of quality of large transformers has been ensured in the USSR by strict specialization of producers. All large transformers have been produced by the Zaporozhye Transformer Plant (ZTZ). Transformers for the Russian power industry are produced by the Moscow Electric Plant (MZ). Operational ex