外文翻译---基于实时频率特性的AGC方案研究
《外文翻译---基于实时频率特性的AGC方案研究》由会员分享,可在线阅读,更多相关《外文翻译---基于实时频率特性的AGC方案研究(22页珍藏版)》请在毕设资料网上搜索。
1、PDF外文:http:/ 第 1 页 附录 英文原文: A Study on AGC Scheme Based on Real Time Frequency Characteristics Hyun-ShinPark, Chungnam National University, Korea Chungnam National University, Korea kjkimcnu.ac.kr Abstract- Automatic generation control (AGC) has been one o
2、f the important issues in the operation of local area and interconnected power systems. AGC provides power demand signals for AGC power generators to control frequency. In AGC, some variables of power system such as frequency and power generation are measured to calculate the area control error (ACE
3、). The ACE value is an important factor of AGC performance. Generally, ACE value is determined by a constant frequency bias factor of power system or 1% of load method. The ACE value based on the constant frequency bias factor or1% of load method, however, may not represent the real time status of p
4、ower system correctly. The incorrect ACE value is a cause of over regulation of power system. This paper presents the method to decide actual frequency bias factor on real time frequency characteristics. In this paper, the actual frequency bias factor is determined by the measured variables such as
5、generator power output change and frequency deviation due to disturbance of power system. The actual frequency bias factor calculated is used to determine the ACE of power system. The AGC divides the calculated ACE among AGC power generators periodically. The period is determined by the time of reco
6、vered frequency. This paper also presents the simulation results for the power system model about the proposed AGC scheme. The simulation results show that the performance of AGC is improved when the proposed AGC scheme is applied to AGC. I. INTRODUCTION The scheduling and control of power ge
7、neration are vital aspects in the daily operation of power systems. Generally, energy management system is provided to control the electrical power output so as to supply ever changing system load for power as economically as possible. Automatic generation control (AGC) program 毕业设计(论文)专用纸 &n
8、bsp;第 2 页 operating within energy management system can provide the necessary means to the system operators. The AGC has been one of major issues in the operation of local control area systems and interconnected power systems for several years. Four basic objectives of power system operation d
9、uring normal operating conditions are associated with AGC: 1) matching total system generation to total system load; 2) regulating system electrical frequency error to zero; 3) distributing system generation among control areas so that net area tie flows match net area tie flow schedules
10、; 4) distributing area generation among area generation sources so that area operating costs are minimized 1. For the isolated control area, the main function of AGC is to restore the system electrical frequency to nominal frequency because there is no tie line flow among control areas 2. AGC
11、uses some field data measured through the supervisory control and data acquisition (SCADA) system which is usually implemented in energy management system. The measured data include power output of units; tie line power flow and electrical frequency of control area, etc. The power generation d
12、emand signals from the AGC function are provided to the related power generation units through SCADA system. In AGC program, the frequency of power system and interchanged power flow among control areas are used to determine area control error (ACE) value. ACE is critical for operation of AGC. In a