1、1 220KV 变电所电气部分设计 摘摘 要:要:本文阐述了设计建设一座 220KV 降压变电所的方案。首先,通过分析原始资料确定主变 形式。然后在对经济和技术方面进行比较后制定出的主接线方案。再次,选取短路点,并对各短路 点进行短路电流计算。 最后, 按各电压等级的额定电压和最大持续工作电流进行设备的选择和校验。 关键词:关键词:变电所;电气主接线;短路电流;电气设备选择 The Design of 220KV Electrical Substation Abstract: A program for the design of the building of a 220 KV antihy
2、pertensive transformer substation is described in this paper. Firstly, through the analysis of raw data the main form of change is determined. After the comparison in economy and technology the optimal program for main wiring is designed. Secondly, select the point of short-circuit and calculate the
3、 current of these short-circuit points. Finally, according to the rated voltage and the maximum persistent current of differential levels, the choice of equipment and calibration is completed. Key Words: substation; electric main wiring; short-circuit current; the selection of electric equipment 1 引
4、言 本所位于市郊,地势平坦,交通便利,具有 220KV、110KV、及 10KV 三个电压等 级,110KV 侧以接受功率为主,10KV 侧主要用于所用电及无功补偿。本次所设计的变 电所是一般变电所,采用两台 OSFPS7-120000/220 型三绕组有载调压变压器,容量为 100/100/50,互为备用。220KV 侧共有 8 回,本期 4 回最终 4 回,110KV 侧也有 11 回, 本期 5 回最终 6 回,10KV 侧本期 12 回最终 16 回。因此 220KV 及 110KV 主接线最后 方案采用双母线带旁母接线方式,正常运行时旁母不带电。 本变电所配电装置采用普通中型配电装置,220KV 及 110KV 均采用断路器单列布 置,将隔离开关放置母线下,使与另一级隔离开关电气距离增大,缩短配电装置的纵向 距离。 主变中性点及出线均装设避雷器,中性点经隔离开关直接接地,并装设两段零序保 护及放电间隙保护。 本次论文设计是以我国现行的各有关规范规程等技术标准为依据, 所设计是一次初 步设计,根据任务书提供的原始资料,参照有关资料及书籍,对各种方案进行比较而得 出 。 2