1、内容提要 根据设计任务书的要求,本次设计为 110kV 变电站电气一次部分初 步设计。该变电站设有两台主变压器,站内主接线分为 110kV、35kV 和 10kV 三个电压等级。各个电压等级分别采用单母线分段接线、单母线分 段带旁母接线和单母线分段接线。 本次设计中进行了电气主接线的设计、主要电气设备选择及校验(包 括断路器、隔离开关、电流互感器、电压互感器、母线等)、各电压等级 配电装置设计、直流系统设计以及防雷保护的配置。 本设计以35110kV 变电所设计规范、供配电系统设计规范、 35110kV高压配电装置设计规范等规范规程为依据,设计的内容 符合国家有关经济技术政策, 所选设备全部为
2、国家推荐的新型产品,技术先进、运行可靠、经济合理。 SUMMARY From the guide of engineering design assignment, we have to design primary power-system of 110kV substation and draw main electrical one-line diagram and others. There are two main transformer in the substation in which main electrical connection can be divided into
3、 three voltage grades: 110kV, 35kV with 10kV.It deposits sectionalized single bus bar scheme, sectionalized single and transfer bus bar and sectionalized single bus bar scheme per grade. There is also a design for main electrical connection in this engineering, the calculation for short-circuit elec
4、tric current, the selection of electrical device and calibration (including circuit breaker, isolator, current transformer, potential transformer ,bus bar etc.) and the design for distribution installation per. voltage grade, direct current system and lightning protection is also included. 目 录 前言1 第
5、 1 章 原始资料2 第 2 章 电气主接线设计4 第2.1 节 主接线的设计原则和要求 4 第2.2 节 主接线的设计步骤6 第2.3 节 本变电站电气主接线设计 7 第 3 章 变压器选择11 第3.1 节 主变压器选择11 第3.2 节 站用变压器选择12 第 4 章 短路电流计算13 第4.1 节 短路电流计算的目的 13 第4.2 节 短路电流计算的一般规定13 第4.3 节 短路电流计算的步骤14 第4.4 节 短路电流计算结果15 第 5 章 直流系统设计17 第5.1 节 直流系统概述17 第5.2 节 直流系统的电压等级18 第5.3 节 直流系统的接线方式18 第5.4 节 本变电站直流系统设计 19 第 6 章 高压电器设备选择20 第6.1 节 电器选择的一般条件20 第6.2 节 高压断路器的选择22 第6.3 节 隔离开关的选择24 第6.4 节 电流互感器的选择25 第6.5 节 电压互感器的选