1、 2011届毕业设计(论文) 题 目:某酒店消防水系统设计 专 业: 消防工程 班 级: 消防 1101 2015 年 6 月 I 七层酒店酒店消防水系统设计 摘要 随着现代经济发展, 宾馆酒店在生活中变得常见普遍。 宾馆酒店类建筑人员流动性大, 室内装修可燃物多,火灾隐患多等特点决定了这类场所对消防系统要求很高。本课题针对 某酒店进行消防水系统。 在这次设计中,工程为七层酒店商用低层建筑,该酒店无地下层,地上共七层,一层 为酒店大厅,二层为餐厅和娱乐场所,三到七层为客房。根据相关设计规范要求该建筑为 二类建筑,危险级别为轻危险级。酒店内设置室内消火栓,设计流量为 15L/s。自动喷水 灭火系
2、统采用闭式湿式自动喷水灭火系统,设计流量为 30L/s,喷头选取68闭式吊顶型 玻璃球喷头,设计扬程为 100mH2O。本次设计主要是基于室内消火栓系统和水喷淋系统 的设计,包括基本分类,组成部分,设计原则,然后详细介绍主要设计流程和计算参数, 最后根据所设计的水系统进行设计总结。 关键词关键词:酒店 消火栓系统 自动喷水灭火系统 II Design of fire water system on seven-story hotel ABSTRACT Hotels appear to be more and more common in our lives with the increasin
3、g development of modern economy, accompanied by a high demand in fire extinguishing system due to the tremendous mobility of its faculty, large amount of inflammable materials in interior decoration, highly fire risks and so on. The project in this design is a seven-floor commercial low-rise buildin
4、g, with the seven floors on the ground excluding those sub levels. The first floor is the lobby of the hotel, the second floor is the restaurant and entertainment places, and the other floors are guest rooms. It was required to be the Type Two building according to those devising rule, with slight l
5、evel of dangers. There would be fire hydrant of 15L/s indoors. While the sprinkler system is in closed wet system, which is of 30L/s flow. And its sprayer is closed hung in 68, with its lift of 100mH2O. This design, based on fire extinguishing system and sprinkler system, includes its fundamental cl
6、assifications, components, design principles, and then describes its main design procedures and calculating parameters, finally come to the overall fire extinguishing budgets of water supply system. Key words: hotel;fire extinguishing system; sprinkler system. 目录 摘要摘要 . I ABSTRACT . II 第第 1 章章 概述概述 .1 1.1 研究背景.1 1.2 消防给水系统概况.2 1.3 设计内容.2 1.3.1 设计规范 .2 1.3.2 法律规范 .2 1.3.3 工程概况 .3 1.3.4 消火栓系统设计内容4 1.3.5 自动喷水灭火系统设计内容 .4 第第 2 章章 消防水系统消防水系统 5 2.1 消火栓给水系统 5 2.1.1 室外消火栓5 2.1.2 室内消火栓7 2.1.3 消火栓